Incident Name Incident Report Report Date/Time Facility Name Facility Address Affected Counties Reporter Name Reporter Title Reporter E-mail Reporter Phone Reporter Role Contact Name Contact Phone Contact E-mail Latitude Longitude Release Start Date/Time On-going Release Release End Date/Time Migrated Off-Site (Y/N) Migrated Counties Map Display
1902 Breckinridge Blvd. Blockage in gravity sewer caused minor overflow at manhole. 07/28/2017 14:51 EDT Flming Island WWTP Collection System 1902 Breckinridge Blvd.; Directions: 1233 feet south of intersection of CR220 and Breckinridge Blvd.; Middleburg FL; 32068 Clay Dennis R Martin Wastewater Superintendent dmartin@clyutility.org (904) 626-3893 Operator Of the Facility Dennis R Martin (904) 626-3893 dmartin@clayutility.org 30.097753 -81.761809 07/28/2017 09:15 EDT No 07/28/2017 13:20 EDT Incident Location
Sanitary Sewer Overspill At 7:18am a SSO was reported on Central Industrial Drive. Arrived onsite around 7:40am where a hole appeared. Immediately staff arrived with vacuum truck and SSO Trailer. Started cleanup process using lime washed down area and collected the water from storm drain. Station back on line 1:10pm 07/28/2017 12:48 EDT City of Riviera Beach 600 West Blue Heron Blvd; Directions: North of Blue Heron Blvd & central Industrial Drive; Riviera Beach FL; 33404 Palm Beach Joseph Jackson Chief Water/Sewer Mechanic adavis@rivierabch.com (561) 845-3485 Operator Of the Facility Larry Brown (561) 845-4177 lbrown@rivierabch.com 26.788995 -80.095906 07/25/2017 07:15 EDT No 07/25/2017 13:10 EDT Incident Location
Sanitary Sewer Overspill July 19, 2017 at 9:44pm sanitary sewer overspill occurred at Lift Station #50 into a catch basin north of the station. The cause of the spill was from a F.P.L. power failure which caused the pumps to fail which lead to wet well overflowing. 07/28/2017 12:28 EDT City of Riviera Beach 600 West Blue Heron Blvd; Directions: 900 Avenue U and Martin Luther King Blvd. north; Riviera Beach FL; 33404 Palm Beach Allen J. Davis Superintendent adavis@rivierabch.com (561) 845-4185 Operator Of the Facility Joseph Jackson (561) 845-3485 jjackson@rivierabch.com 26.771777 -80.084063 07/19/2017 21:45 EDT No 07/19/2017 22:40 EDT Incident Location
Wastewater Spillage Sanitary Sewer Overspill at LS#20 due to old asbestos cement pipe collapsed. The 8" line was discovered Thursday morning at 7:00am. SSO Procedures followed, staff started cleaning process by using vacuum truck and SSO Trail. Sample taken, Lime applied. Completed at 1:43pm. 07/28/2017 11:54 EDT City of Riviera Beach 600 West Blue Heron Blvd; Directions: North of Blue Heron Blvd and Central Industrial Drive.; Riviera Beach FL; 33404 Palm Beach Allen J. Davis Superintendent adavis@rivierabch.com (561) 845-4185 Operator Of the Facility Joseph Jackson (561) 845-3485 jjackson@rivierabch.com 26.788665 -80.095879 07/27/2017 07:00 EDT No 07/27/2017 13:45 EDT Incident Location
MSP - LOADER - NPDES OUTFALL 004 - 07172017 A front-end loader, operated by a Mosaic employee, traveling along a mine road, broke through a berm and overturned within an NPDES out-fall conveyance ditch, which created a sheen on the discharging water. There was visible indication that sheen was passing through the out-fall's V-notch weir. It is undetermined at this time whether the sheen is coming from the exterior of the machine being washed by the discharge effluent; or, if the diesel tank has been compromised. The amount of released fuel has not been determined at this time. 07/28/2017 10:20 EDT Mosaic South Pasture Mine 2220 Mineview Road; Bowling Green FL; 33834 Hardee Santino Provenzano Sr. Mgr. EHS santino.provenzano@mosaicco.com (863) 486-3762 Sr. Mgr. EHS Wayne Albritton (863) 781-6379 wayne.albritton@mosaicco.com 27.582454 -81.948909 07/17/2017 05:55 EDT No 07/17/2017 08:45 EDT Y Hardee, Incident Location
1302 NW 169th ave - 6" FM break on 7-27-17 at 1230 pm a call was received pertaining to a leak in grassy area between curb and sidewalk, it was deemed to be sewer line was isolated and system shut down to make repair. In time of incident it was estimated that 100 gallons of raw sewer was discharged to the drainage box 200 ft south of break site which dumped into retention lake 50ft to the west of the box. The line was dug up and bad section was removed and replaced. System was leak checked and normal flow resumed. Installed proper bedding and backfilled area with compaction. 07/28/2017 08:16 EDT City of Pembroke Pines 8300 S palm Dr; Pembroke Pines FL; 33025 Broward Ron Abel D&C supervisor ron.abel@ch2m.com (321) 288-0037 Operator Of the Facility Dan Stark (478) 361-5244 dan.stark@ch2m.com 26.016879 -80.373262 07/27/2017 12:30 EDT No 07/27/2017 13:00 EDT Incident Location
Valrico AWWTF, 1167 N. Dover Road, Dover FL, 33527 On 7/27/17 at 12:00am the Valrico AWWTF lost communication with the NTU and pH meters on SCADA and was not being trended or recorded, however they were working in the field. From 12:00am on 7/27 to 7:00am on 7/27 our NTU and pH readings were not being trended or recorded. The on duty operator did not notice this communication fault. A NTU and pH comparison was taken at 11:20pm on 7/26 and the lab NTU reading was 0.44 and the pH reading was 7.34. One field reading was taken at 05:10am and the NTU and pH was 0.42 and 7.34, respectively. The operators started 15 minute NTU and pH readings at 7:00am until 8:30am on 7/27 and the NTU readings were between 0.40-0.46 and the pH readings were between 7.37-7.40. The SCADA trends for July 26th showed NTU readings between 0.28-0.48 and pH between 7.33-7.43. The SCADA trending for UVT (transmittance/effluent clarity) for the UV system was between 66.09%-66.78% from 12:00am to 7:00am on 7/27. Also, our effluent TSS for this day was 0.1 mg/L. The amount of water that was not being trended or recorded for NTU and pH was 1,600,000 gallons which went to the reclaim tanks. Regulatory Agency notification was made to Erica Peck with DEP at 9:10am, David with EPC at 9:15am, and State Warning Point at 9:20am, case #2017-5649. There is no immediate impact to residences or businesses. 07/27/2017 16:49 EDT Valrico AWWTF, 1167 N. Dover Road, Dover FL, 33527 FL0040983  FL Hillsborough JON JOHANSON PROJECT MANAGER II JOHANSONJ@HILLSBOROUGHCOUNTY.ORG (813) 209-3088 PROJECT MANAGER II RICHARD CUMMINGS (813) 209-3003 CUMMINGSR@HILLSBOROUGHCOUNTY.ORG 27.958369 -82.229953 07/27/2017 00:00 EDT No 07/27/2017 07:00 EDT Incident Location
Diesel Fuel Release An MCI Express truck spilled approximately 50 gallons of diesel fuel to the asphalt lot and nearby storm drain. Approximately 300ft x 20ft of asphalt area was impacted. A contractor responded to perform cleanup operations. Granular absorbents were placed to the impacted asphalt lot. The used absorbents and waste debris were containerized into (1) 55 gallon metal drum. Approximately 800 gallons of diesel impacted water was pumped from the affected storm drain using a vac-truck. All waste was taken offsite with the contractor for disposal. 07/27/2017 13:00 EDT Coca-Cola Beverages Florida 3350 Pembroke ; Hollywood FL; 33021 Broward Philip Blashford Project Manager pblashford@ertsonline.com (440) 349-2700 3rd Party agent for Coca-Cola Philip Blashford (440) 349-2700 pblashford@ertsonline.com 25.994861 -80.176446 07/24/2017 04:40 EDT No 07/24/2017 07:30 EDT N Incident Location
Sump Integrity Test While conducting our annual storage tank testing the STP sump for the gasoline tank failed. We are currently investigating if a release has occurred. Palm Beach CNTY Schools-West Trans 1901 NW 16th Ste. Belle Glade, FL 33430-1201 Facility ID: 8630624 07/27/2017 12:31 EDT Palm Beach CNTY Schools-West Trans 1901 NW 16th St. ; Belle Glade FL; 33430 Palm Beach Anne P. Meador Environmental Specialist anne.meador@palmbeachschools.org (561) 684-5142 Owner Of the Facility Anne Meador (561) 684-5142 anne.meador@palmbeachschools.org 26.703176 -80.682893 07/26/2017 15:00 EDT Yes Incident Location
Sewer spill Pineapple Park community Lift station lost power causing the gravity system to surcharge during a force main condition assessment. Manholes over flowed spilling about <500 gal. The spill went into a storm drain that cause a body of water to be affected. Location of the incident was on 3 streets : Delphia, Market, New York and cross street Dock. Estimated affected area: 3 manholes 5'x5' each and 60' area storm drain. Cleaned area with lime, vac truck and disinfectant. Put turbidity barriers a the outflows at the stub canal. 07/27/2017 10:05 EDT West Palm beach  FL Palm Beach Charles L Phoenix Jr Superintendent Sanitary Collection CPhoenix@wpb.org (561) 822-2181 Operator Of the Facility Charles L Phoenix Jr (561) 822-2181 Cphoenix@wpb.org 26.695629 -80.063921 07/26/2017 12:30 EDT No 07/26/2017 15:30 EDT Incident Location