Incident Name Incident Report Report Date/Time Facility Name Facility Address Affected Counties Reporter Name Reporter Title Reporter E-mail Reporter Phone Reporter Role Contact Name Contact Phone Contact E-mail Latitude Longitude Release Start Date/Time On-going Release Release End Date/Time Migrated Off-Site (Y/N) Migrated Counties Map Display
sanitary sewer overflow sanitary sewer main line stoppage causing the cleanout to overflow 11/08/2017 14:32 EST East Plant WPC 1985 Sever Dr; Directions: S. Hercules and Sever Dr.; clearwater FL; 33756 Pinellas Rose Lara Supervisor ll rose.lara@myclearwater.com (727) 562-4960 supervisor Rose Lara (727) 562-4960 rose.lara@myclearwater.com 19.336204 -49.578516 11/08/2017 11:15 EST No 11/08/2017 11:50 EST Incident Location
Falkenburg AWWTP 102 N. Falkenburg Rd On November 8, 2017 at 11:30AM a mechanic reported flow was coming out of the west reject tank access hatch. The Influent valve for the west reject had been closed for one week prior so the tank could be emptied for a structural engineer inspection. The effluent or suction side to the pumps was obviously not closed. The east tank back filled the west tank to the open access hatch. Approximately 120,000 gallons of partially treated effluent did flow out into an onsite storm water drain and into an onsite storm water pond. The flow was stopped and the hatch was reinstalled and the tank is in service. Regulatory Agency notification was made at to the DEP via telephone at 12:39 PM and the EPC at 12:33 PM. The state warning point was also notified and here is the incident number, 2017- 9543 There is no immediate impact to residences or businesses. 11/08/2017 14:01 EST Falkenburg AWWTP Permit Number: FL0040614  FL Hillsborough JON JOHANSON PROJECT MANAGER II JOHANSONJ@HILLSBOROUGHCOUNTY.ORG (813) 209-3088 PROJECT MANAGER II RICHARD CUMMINGS (813) 209-3003 CUMMINGSR@HILLSBOROUGHCOUNTY.ORG 27.953018 -82.340305 11/08/2017 11:30 EST No 11/08/2017 12:30 EST Incident Location
Santa Rosa Trunk Line Leak Leak on Santa Rosa Trunk Line discovered at 11:10 AM on November 7, 2017. Area was immediately bermed; estimated small amount of produced water reached Bray Mill Creek (estimated to be less than 2 BBLs). No sheen was observed in creek. Booms were proactively deployed downstream, but no evidence of oil was observed in the creek. 11/08/2017 10:51 EST Breitburn Operating LP 5415 Oil Plant Road; P.O. Box 889; Directions: Located1.5 miles West of Jay Florida; Jay FL; 32565 Santa Rosa Larry Dilmore EHS Coordinator Larry.Dilmore@breitburn.com (850) 758-0538 EHS Coordinator Antonio D'Amico (213) 225-0252 Antonio.D'Amico@breitburn.com 30.962561 -87.151484 11/07/2017 11:10 EST No 11/07/2017 11:45 EST Incident Location
Wastewater Spill Light House Point Wastewater spill due to failed 12 discharge pipe gasket, at 4115 NE 22nd Avenue in Light House Point, FL. The gasket was repaired and the area was sanitized with HTH. The estimated volume of wastewater spilled was 200 gallons, the amount recovered was 100 gallons. The discharge did not impact a water body. 11/07/2017 15:58 EST Lift Station 224 4115 NE 22nd Avenue; Directions: Latitude: 26.282221200 Longitude: -80.093355100; Light house Point FL Broward Mike Kelly Utilities Superintendent mikelly@broward.org (954) 831-0821 First Responder Mike Kelly (954) 831-0821 mikelly@broward.org 26.281143 -80.091545 11/07/2017 07:45 EST No 11/07/2017 08:15 EST Incident Location
Public Sanitary Sewer Overflow-City of Orlando On 11/07/17 at 3:45 AM, the City of Orlando Conserv I Water Reclamation Facility experienced an overflow due directly to the failure of a transducer affecting pump controls and operation. Approximately 19,320 gallons of sewer overflowed and entered two self contained retention ponds. City crews stopped the sewer overflow at 3:58 AM, the affected transducer was replaced and the normal flow was restored. A necessary back up system was installed to prevent issues in the future. All areas impacted by the overflow were sanitized, cleaned and any material remaining in the retention ponds was pumped out and returned to the collection system. 11/07/2017 14:38 EST City of Orlando Conserv I Water Reclamation Facility 11401 Boggy Creek Rd; Directions: From Orlando on Central Florida Greenway Travel south on Central Florida Greenway to I-4 take exit 17B. Turn right/north onto Boggy Creek Rd and continue north for 2.6 miles. Turn right/east onto Robert E Johnson Blvd.; Orlando  FL; 32824 Orange Jeffrey Environmental Specialist jeffrey.hargrove@cityoforlando.net (321) 278-1722 Authorized Representative for the City of Orlando Daniel Friedline (407) 246-2657 daniel.friedline@cityoforlando.net 28.401282 -81.327425 11/07/2017 03:45 EST No 11/07/2017 04:00 EST Incident Location
Q259582_SWO 2017-9514_ NW 13th St & 7th Ave The 2" connection for an air relief valve failed causing an overflow from the manhole. The line was isolated within and hour and the flow was ceased. A portion of the spilled volume impacted a storm drain that outfalls into the middle River Waterway. 11/07/2017 11:49 EST GTL Regional Wastewater Facility  FL; 33309 Broward Troy Balint Environmental Program Coordinator tbalint@fortlauderdale.gov (954) 828-7845 Environmental Program Coordinator TROY BALINT (954) 828-7845 tbalint@fortlauderdale.gov 26.141945 -80.152167 11/06/2017 12:35 EST No 11/06/2017 13:30 EST Incident Location
Q258893 Orton Ave & Terramar St Overflow from a 6" clean-out. Blockage was cleared. Approximately 750 gallons overflowed, 100 gallons was recovered. The remaining 600 gallons impacted a storm drain and entered the intracoastal waterway. 11/07/2017 10:56 EST GTL Regional Wastewater Facility  FL; 33309 Broward Troy Balint Environmental Program Coordinator tbalint@fortlauderdale.gov (954) 828-7845 Environmental Program Coordinator Troy Balint (954) 828-7845 tbalint@fortlauderdale.gov 26.131112 -80.106801 11/03/2017 19:15 EDT No 11/06/2017 13:25 EST Incident Location
211 NW 38th Court Pompano Beach Wastewater spill due to a force main break at 211 NW 38th Court in Pompano Beach FL 33069. The force main was isolated and repaired. The estimated volume of wastewater spilled was 1500 gallons. Crews sanitized and cleaned up the area before leaving the site at 9:00 p.m. 11/07/2017 09:26 EST 211 NW 38th Court 211 NW 38th Court; Directions: LATITUDE: 26.277521700 LONGITUDE:-80.1263979000; Pompano Beach FL; 33069 Broward Mike Kelly Utilities Superintendent mikelly@broward.org (954) 831-0821 First Responder Mike Kelly (954) 831-0821 mikelly@broward.org 26.242118 -80.169908 11/06/2017 11:30 EST No 11/06/2017 15:30 EST Incident Location
9330 SR Trinity Medical Hospital ARV Spill Called out due to a sewer break of some sort at the Eastern most entrance to Trinity Hospital. Upon arrival it was found that TR-112-ARV-01 was leaking. Crew was able to close 2" shut off and cease spill. After further investigation of the ARV it was found that the flapper in the head of the ARV had disintegrated causing the spill. Called out sludge trucks to assist with clean up. Retrieved approx. 5000 gals of standing liquids from the field. Spill also entered a storm drain that leads to a retention pond to the West of the ARV. Pulled 15500 gals of storm/sewer from the retention pond. Spread 200 Lbs. of lime to neutralize the impacted area. Will have retention pond sampled to determine if there is any further actions required for the clean up.Spill volume was calculated by amount retrieved. 11/07/2017 07:00 EST Shady Hills Wastewater Treatment Facility 14220 Hays Road; Directions: PERMIT number: FLA012741; Spring Hill FL; 34610 Pasco James Hircock Environmental Compliance Specialist jhircock@pascocountyfl.net (813) 235-6189 Environmental Compliance Specialist James Hircock (813) 235-6189 jhircock@pascocountyfl.net 28.205703 -82.657985 11/06/2017 13:30 EST No 11/06/2017 14:15 EST Incident Location
Diesel Fuel Release 50 gallons of diesel fuel released to the asphalt only due to a punctured saddle tank on a KLLM Transport Services tractor. 11/06/2017 19:53 EST TA TravelCenter 1024 Highway 301; Baldwin FL; 32234 Duval Matthew Andrle Project Manager mandrle@ertsonline.com (440) 349-2700 Agent for Carrier Matthew Andrle (440) 772-1093 mandrle@ertsonline.com 30.28352 -81.670898 11/06/2017 15:30 EST No 11/06/2017 17:00 EST Incident Location